User Manual Owner's manual

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 91
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
StarterCommand
The parameter provides the Run Command
status to the starter.
Parameter Number 7
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 0x3F07
Default Value 0
Bit
Function
1514131211109876543210
——————————————— X RunForward
—————————————— X RunReverse
————————————— X —— ResetFault
———————— XXXXX Reserved
——————— X ———————— Out00
—————— X ————————— Out01
————— X —————————— Out02
———— X ——————————— Out03
——— X ———————————— Out04
—— X ————————————— Out05
X X ————————————— Reserved
AuxIOStatus
The parameter provides the status of
hardware input/output points.
Parameter Number 8
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 0x3F
Default Value 0
Bit
Function
1514131211109876543210
——————————————— X Pt00
—————————————— X Pt01
————————————— X —— Pt02
———————————— X ——— Pt03
——————————— X ———— Pt04
—————————— X ————— Pt05
XXXXXXXXXX—————— Reserved