User Manual Owner's manual
90 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
StarterStatus
This parameter provides the status of the
starter.
Parameter Number 6
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 0x4FBF
Default Value 0
Bit
Function
1514131211109876543210
——————————————— X TripPresent
—————————————— X — WarningPresent
————————————— X —— RunningForward
———————————— X ——— RunningReverse
——————————— X ———— Ready
—————————— X ————— NetControlStatus
————————— X —————— Reserved
———————— X ——————— CurrentFlowing
——————— X ———————— DLXEnabled
—————— X ————————— KeyPadAuto
————— X —————————— KeyPadOff
———— X ——————————— KeyPadHand
—— X X ———————————— Reserved
— X —————————————— DisconnectClosed
X ——————————————— Reserved