User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 233
CIP Information Appendix B
The table below lists Fault Codes, Fault Text, and Fault Help Strings for Drive
units.
30 Hardware Fault This is a major fault which renders the unit inoperable.
31 Fault 31 —
32 Fault 32 —
33 Fault 33 —
34 Fault 34 —
35 Fault 35 —
36 Fault 36 —
37 Fault 37 —
38 Fault 38 —
39 Fault 39 —
40 Unknown Fault —
41 BrakeOption Brake Option hardware does not match parameter 92 setting.
42 KeypadOption Keypad Option hardware does not match parameter 92 setting.
…
75 Fault 75 —
Table 31 - Fault Codes, Fault Text, and Fault Help Strings for Drive Units
Fault
Code Fault Text Help Text
PF4M
Fault
Code
1Fault 1 —
2 User Defined User defined trip has occurred.
3 Motor Overload The load has drawn excessive current. 7
4 Drive Overload 150% load for 1 min. or 200% load for 3 sec. exceeded. 64
5 Phase U to Gnd A Phase U to Ground fault detected between drive and motor. 38
6 Phase V to Gnd A Phase V to Ground fault detected between drive and motor. 39
7 Phase W to Gnd A Phase W to Ground fault detected between drive and motor. 40
8 Phase UV Short Excessive current detected between phases U and V. 41
9 Phase UW Short Excessive current detected between phases U and W. 42
10 Phase VW Short Excessive current detected between phases V and W. 43
11 Ground Fault A current path to earth ground at one or more output terminals. 13
12 Stall Trip The drive is unable to accelerate the motor. 6
13 Switched Power Indicates the loss of switched control power.
Not available in units with Integrated Power Supply
14 Under Power Trip Indicates the internal power supply is below its working level.
Available in units with Integrated Power Supply only.
15 Sensor Short Flags a miswired hardware input point.
16 Output Short Flags a miswired hardware output point.
Table 30 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers
Fault
Code Fault Text Help Text