The table below lists Fault Codes, Fault Text, and Fault Help Strings for DOL
and Reversers.
Service Code
Implemented for:
Service NameClass Instance
0x0E Yes Yes Get_Attribute_Single
0x10 Yes No Set_Attribute_Single
Table 30 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers
Fault
Code Fault Text Help Text
1Fault 1 —
2 User Defined User defined trip has occurred.
3 Overload Trip Load has drawn excessive current based on trip class selected.
4Fault 4 —
5 Phase Loss Trip Indicates missing supply phase. This fault can be disabled.
6 Jam Trip Motor current above jam level for more than jam trip delay time.
7 Underload Trip Motor current below UL level for more than UL trip delay time.
8Fault 8 —
9Fault 9 —
10 Fault 10 —
11 Fault 11 —
12 Stall Trip Motor current above stall trip level during motor starting.
13 Switched Power Indicates the loss of switched control power.
Not available in units with Integrated Power Supply.
14 Under Power Trip Indicates the internal power supply is below its working level.
Available in units with Integrated Power Supply only
15 Sensor Short Flags a miswired hardware input point.
16 Output Short Flags a miswired hardware output point.
17 Fault 17 —
18 Fault 18 —
19 Phase Imbalance Indicates an imbalanced phase current.
20 Fault 20 —
21 Aux Power Loss Auxiliary Power was lost or dipped below the minimum threshold.
Not available in units with Integrated Power Supply
22 Fault 22 —
23 Fault 23 —
24 Fault 24 —
25 Fault 25 —
26 Fault 26 —
27 NonVol Memory This is a major fault which renders the unit inoperable.
28 Fault 28 —
29 Fault 29 —