User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 225
CIP Information Appendix B
Analog Input Point Object
CLASS CODE 0x000A (Implemented in Bulletin 294D units only)
The following class attributes will be supported for the Analog Input Point
Object:
Two instances of the Analog Input Point Object will be supported.
CommandFreq from Assembly 154 is placed in the value attribute when
it is consumed.
The following common services will be implemented for the Analog Input Point
Object:
Analog Output Point Object
CLASS CODE 0x000B (Implemented in Bulletin 294D units only)
The following class attributes will be supported for the Analog Output Point
Object:
One instance of the Analog Output Point object will supported. It will represent
the Frequency command. CommandFreq from Assembly 154 is placed in the
Value Attribute when it is consumed. The Value Attribute can then be
overwritten by DeviceLogix.
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 2
2 Get Max Instance UINT 1
Attribute ID Access Rule Name Data Type Value
3Get Value INT Default = 0
8 Get Value Data Type USINT 0 = INT
Service Code
Implemented for:
Service NameClass Instance
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 2
2 Get Max Instance UINT 1
Attribute ID Access Rule Name Data Type Value
3 Get/Set Value INT 0 = Default
8 Get Value Data Type USINT 0 = INT
129 Get/Set Input Binding
STRUCT:
USINT
Array of USINT
Size of Appendix I encoded path
Appendix I encoded path
NULL path means attribute 3 drives the output.
Otherwise, this is a path to a bit in the Bit Table.