Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 217
CIP Information Appendix B
Multiple instances of the Connection Object will be supported, instances 1, 2,
and 4 from the group 2 predefined master/slave connection set, instances 5-7 will
be available explicit UCMM connections, and instances 8-11 will act as ZIP
consumers.
Instance 1
Instance 1 is the Predefined Group 2 Connection Set Explicit Message
Connection. The following instance 1 attributes will be supported:
Instance 2
Instance 2 is the Predefined Group 2 Connection Set Polled I/O Message
Connection. The following instance 2 attributes will be supported:
Attribute ID Access Rule Name Data Type Value
1 Get State USINT 0=nonexistant
1=configuring
3=established
4=timed out
2 Get Instance Type USINT 0=Explicit
Message
3 Get Transport Class Trigger USINT 0x83 - Server, Transport
Class 3
4 Get Produced Connection ID UINT 10xxxxxx011
xxxxxx=node address
5 Get Consumed Connection ID UINT 10xxxxxx100
xxxxxx=node address
7 Get Produced Connection Size UINT 0x61
8 Get Consumed Connection Size UINT 0x61
9 Get/Set Expected Packet Rate UINT in milliseconds
12 Get Watchdog Action USINT 01 = auto delete
03 = deferred delete
Attribute ID Access Rule Name Data Type Value
1 Get State USINT 0=nonexistant
1=configuring
3=established
4=timed out
2 Get Instance Type USINT 1=I/O Connection
7 Get Produced Connection Size UINT 0 to 8
8 Get Consumed Connection Size UINT 0 to 8