User Manual Owner's manual

214 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Appendix B CIP Information
Instance 151
Instance 151 is the compact input (Produced) Assembly for Bulletin 290D/
291D starters.
Instance 152
Instance 152 is the Exhaustive Starter Status Assembly for Bulletin 290D/291D
starters.
Instance 151 "Compact Status" – Compact Produced Assembly for Bulletin 290D/291D Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 CurrentFlowing NetControlStatus Ready RunningReverse RunningForward WarningPresent TripPresent
1 DisconnectClosed KeyPadHand KeyPadOff KeyPadAuto DLXEnabled
2 Pt05 Pt04 Pt03 Pt02 Pt01 Pt00
3
4 Pt07DeviceOut Pt06DeviceOut Pt05DeviceOut Pt04DeviceOut Pt03DeviceOut Pt02DeviceOut Pt01DeviceOut Pt00DeviceOut
5 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt12DeviceOut Pt11DeviceOut Pt10DeviceOut Pt09DeviceOut Pt08DeviceOut
Instance 152 "Starter Stat" – DeviceLogix Produced Assembly for Bulletin 290D/291D Starters
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 CurrentFlowing NetControlStatus Ready RunningReverse RunningForward WarningPresent TripPresent
1 DisconnectClosed KeyPadHand KeyPadOff KeyPadAuto DLXEnabled
2 Pt05 Pt04 Pt03 Pt02 Pt01 Pt00
3
4 Pt07DeviceOut Pt06DeviceOut Pt05DeviceOut Pt04DeviceOut Pt03DeviceOut Pt02DeviceOut Pt01DeviceOut Pt00DeviceOut
5 Pt15DeviceOut Pt14DeviceOut Pt13DeviceOut Pt12DeviceOut Pt11DeviceOut Pt10DeviceOut Pt09DeviceOut Pt08DeviceOut
6 An00DeviceOut (low byte)
7 An00DeviceOut (high byte)
8
Parameter 1 – PhaseL1Current
9
10
Parameter 2 – PhaseL2Current
11
12
Parameter 3 – PhaseL3Current
13
14
Parameter 4 – AverageCurrent
15
16
Parameter 5 – %ThermalUtilized
17
18
Parameter 11 – SwitchedVolts
OutputSourceV (IPS units)
19
20
Parameter 12 – UnswitchedVolts
SensorSourceV (IPS units)
21