User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 205
CIP Information Appendix B
Identity Object
CLASS CODE 0x0001
The following class attributes are supported for the Identity Object:
One instance of the Identity Object will be supported for Bulletin 290D and Bulletin
291D; 2 for Bulletin 294D. The following table shows what each instance will represent.
Each instance of the Identity Object will contain the following attributes:
➊ See product code definitions in Tab le 29, Product Codes and Name Strings.
Extended Device Status Field (bits 4-7) in “Status” Instance Attribute 5.
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1
2 Get Max Instance UINT 1 for DOL/Reverser; 2 for VFD
Instance Name Revision Attribute
1 Main Control Board The firmware rev of the main control board operating system
2 PowerFlex 4M (294D only) The firmware revision of the PowerFlex 4M
Attribute ID Access Rule Name Data Type Value
1 Get Vendor UINT 1
2 Get Device Type UINT 22
3
➊ Get Product Code UINT Product Code specific.
4 Get
Revision
Major Revision
Minor Revision
Structure of:
USINT
USINT
5 Get Status WORD
Bit 0 - 0 = Not Owned; 1 = Owned by Master
Bit 2 - 0 = Factory Defaulted; 1 = Configured
Bits 4-7 – Extended Status (see table below)
Bit 8 - Minor Recoverable fault
Bit 9 - Minor Unrecoverable fault
Bit 10 - Major Recoverable fault
Bit 11 - Major Unrecoverable fault
6 Get Serial Number UDINT Unique number for each device
7
➊ Get
Product Name
String Length
ASCII String
Structure of:
USINT
STRING
Product Code specific
8 Get State USINT Returns the value 3 = Operational
9 Get
Configuration
Consistency Value
UINT Unique value depending on output of the parameter
checksum algorithm.
102 Get Build UDINT Firmware Build Number
Value Description
0 Self-testing or unknown
1 Firmware update in progress
2 At least one faulted I/O connection
3 No I/O connections established