User Manual Owner's manual

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 153
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
OptionMatch
If product options do not match value, a
hardware fault will occur.
Parameter Number 92
Access Rule GET/SET
Data Type DWORD
Group Advance Config
Units
Minimum Value 0
Maximum Value 0xffffffff
Default Value 0
Bit
Function
4-313210
X KeypadPreesent
——X—
KeypadNotPresent
X BrakePresent
X BrakeNotPresent
X ———— Reserved
AutobaudEnable
Autobaud enabled when set
0=Disable
1=Enable
Parameter Number 100
Access Rule SET
Data Type BOOL
Group Network
Units
Minimum Value 0
Maximum Value 1
Default Value 1
ConsumedIOAssy
Selects the format of the I/O data
consumed
294 default = 154
Parameter Number 101
Access Rule SET
Data Type USINT
Group Network
Units
Minimum Value 3
Maximum Value 154
Default Value 154