User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 145
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
Figure 36 - Skip Frequency Band
SkipFrequency
Sets the frequency at which the drive will
not operate.
Parameter Number 73
Related Parameters 74
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units Hz
Minimum Value 0
Maximum Value 400 Hz
Default Value 0 Hz
SkipFrqBand
Determines the band width around
Parameter 73 (SkipFrequency). Parameter
74 (SkipFreqBand) is split applying 1/2
above and 1/2 below the actual skip
frequency. A setting of 0.0 disables
this parameter.
Parameter Number 74
Related Parameters 73
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units x.x Hz
Minimum Value 0.0 Hz
Maximum Value 30.0 Hz
Default Value 0.0 Hz
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band