Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
OutNetFaultValue
This parameter determines the state that
starter outputs when an Ethernet fault
occurs and Parameter 54
(OutNetFaultState) is set to 0.
0 = OFF
1 = ON
Parameter Number 55
Access Rule GET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutNetIdleState
This parameter in conjunction with
Parameter 57 (OutNetIdleValue) defines
how the starter outputs will respond when
a network is idle.
0 = GoToIdleValue
1 = HoldLastState
Parameter Number 56
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutNetIdleValue
This parameter determines the state that
starter outputs assumes when the
network is idle and Parameter 56
(OutNetIdleState) is set to 0.
0 = OFF
1 = ON
Parameter Number 57
Access Rule GET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Input00Function
This parameter determines the special
function for User Input 0:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive.
All others are edge sensitive
Parameter Number 58
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 5
Default Value 0