Bulletin 290D/291D/294D Programmable Parameters Chapter 4
FilterOnOff
This parameter determines the input
(which must be absent for this time)
before being reported OFF.
Parameter Number 51
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units msecs
Minimum Value 0
Maximum Value 64
Default Value 0
OutProtFltState
This parameter in conjunction with
Parameter 53 (OutProtFltValue) defines
how the starter outputs will respond
when a fault occurs.
0 = GoToPrFltValue
1 = IgnorePrFlt
Parameter Number 52
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutProtFltValue
This parameter determines how the starter
outputs will be commanded in the event
of a protection fault if Parameter 52
(OutProtFltState) = 0.
0 = OFF
1 = ON
Parameter Number 53
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutNetFaultState
This parameter in conjunction with
Parameter 55 (OutNetFaultValue) defines
how the starter outputs will respond
on an Ethernet fault.
0 = GoToFaultValue
1 = HoldLastState
Parameter Number 54
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0