User Manual Owner's manual

138 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
User I/O Configuration Group
RunNetIdlValue
This parameter determines the state that
starter assumes when the network is idle
and Parameter 47 (RunNetIdlAction) is
set to 1.
0 = OFF
1 = ON
Parameter Number 48
Access Rule GET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 0x3F
Default Value 0
IOPointConfigure
This parameter determines the point
that is configured:
0 = Input
1 = Output
Parameter Number 49
Access Rule GET/SET
Data Type WORD
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 0x3F
Default Value 0
Bit
Function
5 4 3 2 1 0
X Pt00
X Pt01
X Pt02
X Pt03
X Pt04
X Pt05
FilterOffOn
This parameter determines the input
(which must be present for this time)
before being reported ON.
Parameter Number 50
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units msecs
Minimum Value 0
Maximum Value 64
Default Value 0