User Manual Owner's manual
136 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
The functions highlighted are enabled by default
Bit
Function
1514131211109876543210
——————————————— X
OverloadTrip
—————————————— X — PhaseShortTrip
————————————— X —— UnderPowerTrip
———————————— X ———
SensorShortTrip
——————————— X ———— OverCurrentTrip
—————————— X ————— NonVolMemoryTrip
————————— X ——————
ParamSyncTrip
———————— X ———————
DCBusTrip/
OpenDisconnect
——————— X ———————— StallTrip
—————— X —————————
OverTemperature
————— X —————————— GroundFault
———— X ——————————— RestartRetries
——— X ————————————
DriveHdwFault
—— X ————————————— OutputShortTrip
— X —————————————— UserDefinedTrip
X ———————————————
HardwareFltTrip
WarningEnable
This parameter enables a warning
by setting the bit to 1.
Parameter Number 43
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 0xC044
Default Value 0
Bit
Function
1514131211109876543210
—————————————— X X Reserved
————————————— X ——
UnderPowerWarn
—————————— X X X ——— Reserved
————————— X —————— DriveParamInit
—— X — X X X X X ——————— Reserved
——— X ———————————— FanWarning
— X —————————————— DNetPwrWarn
X ——————————————— ConfigWarning