Bulletin 290D/291D/294D Programmable Parameters Chapter 4
Speed Control Group
SpeedReference
Sets the source of the speed reference:
0 = Logix (Network or DeviceLogix)
1 = InternalFreq
Parameter Number 33
Related Parameters 1, 2, 36, 37, 72
Access Rule GET/SET
Data Type UINT
Group Speed Control
Units
Minimum Value 0
Maximum Value 2
Default Value 0
MinimumFreq
Sets the lowest frequency the drive will
output continuously.
Parameter Number 34
Related Parameter 1, 2, 35
Access Rule GET/SET
Data Type UINT
Group Speed Control
Units x.x Hz
Minimum Value 0.0
Maximum Value 400.0
Default Value 0.0
MaximumFreq
Sets the highest frequency the drive
will output.
Parameter Number 35
Related Parameter 1, 2, 34, 35, 139
Access Rule GET/SET
Data Type UINT
Group Speed Control
Units Hz
Minimum Value 0.0
Maximum Value 400
Default Value 60
Stop drive before changing this
parameter.
O
AccelTime1
Sets the rate of acceleration for all speed increases.
Parameter Number 36
Related Parameters 33, 37
Access Rule GET/SET
Data Type UINT
Group Speed Control
Units x.x secs
Minimum Value 0.0
Maximum Value 600.0
Default Value 10.0
Maximum Freq
Accel Time
-------------------------------------- A c c e l R a t e=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 1
0
0
Time
Decel
Time 1
Acceleration
Deceleration