User Manual Owner's manual
128 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
Trip Status Group
TripStatus
This parameter provides the fault
condition that caused any current trip.
Parameter Number 16
Access Rule GET
Data Type WORD
Group Trip Status
Units —
Minimum Value 0
Maximum Value 0xFFFF
Default Value 0
Bit
Function
1514131211109876543210
——————————————— X OverloadTrip
—————————————— X — PhaseShortTrip
————————————— X —— UnderPowerTrip
———————————— X ——— SensorShortTrip
——————————— X ———— OverCurrentTrip
—————————— X ————— NonVolMemoryTrip
————————— X —————— ParamSyncTrip
———————— X ———————
DCBusTrip/
OpenDisconnect
——————— X ———————— StallTrip
—————— X —————————
OverTemperature
————— X —————————— GroundFault
———— X ——————————— RestartRetries
——— X ———————————— DriveHdwFault
—— X ————————————— OutputShortTrip
— X —————————————— UserDefinedTrip
X ——————————————— HardwareFltTrip
WarningStatus
This parameter provides the current
warning condition.
Parameter Number 17
Access Rule GET
Data Type WORD
Group Trip Status
Units —
Minimum Value 0
Maximum Value 0xC044
Default Value 0