126 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
DLXControlStatus
The parameter provides the DeviceLogix
Control Status.
0 = Controlled in Logix Programs
1 = Controlled in local DLX programs.
Parameter Number 10
Access Rule GET
Data Type UINT
Group Basic Status
Units —
Minimum Value 0
Maximum Value 0x1FFF
Default Value 0
Bit
Function:
1514131211109876543210
——————————————— X RunForward
—————————————— X — RunReverse
————————————— X —— Out00
———————————— X ——— Out01
——————————— X ———— Out02
—————————— X ————— Out03
————————— X —————— Out04
———————— X ——————— Out05
——————— X ——————— JogForward
—————— X ————————— JogReverse
————— X —————————— Accel2
———— X ——————————— Decel2
——— X ———————————— Command Freq
X X X ————————————— Reserved
OutputSourceV (IPS)
[SwitchedVolts]
This parameter determines the incoming
switched control voltage across terminals
A1…A2.
(IPS) available voltage on User Output Pin
4 for all I/O points.
Parameter Number 11
Access Rule GET
Data Type UINT
Group Basic Status
Units x.xx Volts
Minimum Value 0
Maximum Value 65535
Default Value 0