User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 125
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Pt00
—————————————— X — Pt01
————————————— X —— Pt02
———————————— X ——— Pt03
——————————— X ———— Pt04
—————————— X ————— Pt05
XXXXXXXXXX—————— Reserved
NetworkStatus
The parameter provides the status
of the network connections.
Parameter Number 9
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 0xDF
Default Value 0
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X ExplicitCnxn
—————————————— X — IOConnection
————————————— X —— ExplicitCnxnFlt
———————————— X ——— IOCnxnFault
——————————— X ———— IOCnxnIdle
———————— X X X ————— Reserved
——————— X ———————— ZIP1Cnxn
—————— X ————————— ZIP1CnxnFlt
————— X —————————— ZIP2Cnxn
———— X ——————————— ZIP2CnxnFlt
——— X ———————————— ZIP3Cnxn
—— X ————————————— ZIP3CnxnFlt
— X —————————————— ZIP4Cnxn
X ——————————————— ZIP4CnxnFlt