User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 123
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
DCBusVoltage
This parameter provides the present DC
bus voltage level.
Parameter Number 5
Access Rule GET
Data Type UINT
Group Basic Status
Units V DC
Minimum Value 0
Maximum Value 1200
Default Value 0
Starter Status
This parameter provides the status
of the starter.
Parameter Number 6
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value OxDFFF
Default Value 0
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X TripPresent
—————————————— X — WarningPresent
————————————— X —— RunningForward
———————————— X ——— RunningReverse
——————————— X ———— Ready
—————————— X ————— NetControlStatus
————————— X —————— NetRefStatus
———————— X ——————— AtReference
——————— X ———————— DLXEnabled
—————— X ————————— KeyPadAuto
————— X —————————— KeyPadOff
———— X ——————————— KeyPadHand
——— X ———————————— KeyPadJogging
—— X ————————————— Reserved
— X —————————————— DisconnectClosed
X ——————————————— BrakeStatus