User Manual Owner's manual
108 Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4 Bulletin 290D/291D/294D Programmable Parameters
StallTripLevel
This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.
Parameter Number 75
Access Rule GET
Data Type UINT
Group Advanced Config.
Units %FLA
Minimum Value 100
Maximum Value 600
Default Value 600
ULInhibitTime
This parameter determines the time
during motor starting that Underload
detection is inhibited.
Parameter Number 76
Access Rule GET
Data Type USINT
Group Advanced Config.
Units secs
Minimum Value 0
Maximum Value 250
Default Value 10
ULTripDelay
This parameter determines the time below
Underload Level before the unit will trip.
Parameter Number 77
Access Rule GET
Data Type USINT
Group Advanced Config.
Units x.x secs
Minimum Value 1
Maximum Value 25.0
Default Value 5.0
ULTripLevel
This parameter determines the
Underload Trip Level as a percentage
of Full Load Amps.
Parameter Number 78
Access Rule GET
Data Type USINT
Group Advanced Config.
Units %FLA
Minimum Value 10
Maximum Value 100
Default Value 50