User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 107
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
JamTripDelay
This parameter determines how much
time above the Jam Level before the unit
will trip.
Parameter Number 71
Access Rule GET
Data Type USINT
Group Advanced Config.
Units x.x secs
Minimum Value 1
Maximum Value 25.0
Default Value 5.0
JamTripLevel
This parameter determines the Jam Trip
Level as a percentage of Full Load Amps.
Parameter Number 72
Access Rule GET
Data Type UINT
Group Advanced Config.
Units %FLA
Minimum Value 50
Maximum Value 600
Default Value 250
JamWarningLevel
This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.
Parameter Number 73
Access Rule GET
Data Type UINT
Group Advanced Config.
Units %FLA
Minimum Value 50
Maximum Value 600
Default Value 150
StallEnabledTime
This parameter determines the time
that stall detection is enabled during
motor starting.
Parameter Number 74
Access Rule GET
Data Type USINT
Group Advanced Config.
Units secs
Minimum Value 0
Maximum Value 250
Default Value 10