User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 105
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
Miscellaneous Configuration Group
Input05Function
This parameter determines the special
function for User Input 5:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊
➊ These choices are level sensitive. All
others are edge sensitive
Parameter Number 63
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units —
Minimum Value 0
Maximum Value 4
Default Value 0
NetworkOverride
This parameter allows for the local logic to
override a Network fault.
0 = Disable
1 = Enable
Parameter Number 64
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
CommsOverride
This parameter allows for local logic to
override an I/O connection timeout.
0 = Disable
1 = Enable
Parameter Number 65
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
KeypadMode
This parameter selects if the keypad
operation is maintained or momentary.
0 = Momentary
1 = Maintained
Parameter Number 66
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0