9-2 Diagnostics
Clear Fault You may clear a fault using the following methods:
Remotely via network communications
A remote reset will be attempted upon detection of a rising edge
(0 to 1 transition) of the “Fault Reset” bit in the various I/O
assemblies. A remote reset will also be attempted upon detection
of the rising edge of the “Fault Reset” parameter.
Locally via the “Reset” button on the LED Status indication
keypad.
Fault Codes Table 9.1 provides a complete reference of the Fault LED indications
for Bulletin 280G/281G and 284G ArmorStart Distributed Motor
Controllers.
Table 9.1 Fault Indication
Blink Pattern
Fault Types
Bulletin 280G/281G Bulletin 284G
1 Short Circuit Short Circuit
2 Overload Trip Overload Trip
3 Phase Loss Phase Short
4 Reserved Ground Fault
5 Reserved Stall
6 Control Power Control Power
7 I/O Fault I/O Fault
8 Over Temperature Over Temperature
9 Phase Imbalance Over Current
10 DeviceNet™ Power Loss DeviceNet™ Power Loss
11 Reserved Internal Communications
12 Reserved DC Bus Fault
13 EEPROM Fault EEPROM Fault
14 Hardware Fault Hardware Fault
15 Reserved Restart Retries
16 Reserved Misc. Fault