User Manual Owner manual
4-32 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
15 StpLogic Out Drive enters Step Logic step with Digit 3 of Command Word (Parameters 240…247).
16 Timer Out
Timer has reached value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2 Level). Use
Parameter 159 or 162 to set threshold.
17 Counter Out
Counter has reached value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2 Level). Use
Parameter 159 or 162 to set threshold.
18 Above PF Ang
Power factor angle has exceeded the value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto
Output 2 Level). Use Parameter 159 or 162 to set threshold.
19 Anlg In Loss Analog input loss has occurred. Program parameter 122 (Analog In Los) for desired action when loss occurs
20 ParamControl
Enables the output to be controlled over the network communications by writing to Parameter 159 (Opto Out 1
Level) or Parameter 162 (Opto Output 2 Level) (0 = Off, 1 = ON).
21 NonRec Fault
Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
22 EM Brk Cntrl
EM Brake is energized. Program Parameter 260 (EM Brk Off Delay) and Parameter 262 (EM Brk On Delay) for
desired action.
159 (Opto Out1 Level)
162 (Opto Out2 Level)
Sets the trip point for the digital output relay if the value of Parameter 158 (Opto
Out1 Sel) or Parameter 161 (Opto Out2 Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.
Parameter Number 159 162
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units —
Minimum Value 0.0
Maximum Value 9999
Default Value 0.0
Options Description
ATTENTION
!
Parameter 192 (Auto Rstrt Tries) is not enabled. A non-
resettable fault has occurred.
Parameters 158 and 161
Setting
Parameters 159 and 161
Min./Max.
60/400 Hz
70/180%
8 0/815V
10 0/100%
16 0.1/9999 sec
17 1/9999 counts
18 1/180°
20 0/1
Opto Out Logic
Determines the logic (Normally Open/N.O. or Normally Closed/N.C.) of the opto
outputs.
Parameter Number 164
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 1
Minimum Value 0
Maximum Value 3
Default Value 0
Option Opto Out1 Logic Opto Out2 Logic
0 N.O. (Normally Open) N.O. (Normally Open)
1 N.C. (Normally Closed) N.O. (Normally Open)
2 N.O. (Normally Open) N.C. (Normally Closed)
3 N.C. (Normally Closed) N.C. (Normally Closed)