Safety Version - User Manual User guide

4-12 Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Starter Protection Group
Breaker Type
This parameter identifies the Bulletin 140M used in this product.
0 = 140M-D8N-C10
1 = 140M-D8N-C25
Parameter Number 22
Access Rule GET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value
PrFlt Reset Mode
This parameter is the Protection Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number 23
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Pr Fault Enable
This parameter enables the Protection Fault by setting the bit to 1.
Parameter Number 24
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 65535
Default Value 64927
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
X Short Circuit
X Overload
X Phase Short
X Ground Fault
X Stall
X Control Power
X IO Fault
X Overtemperature
X Over Current
X Dnet Power Loss
X Internal Comm
X DC Bus Fault
X EEprom
X HW Fault
X Restart Retries
X Misc. Fault