Safety Version - User Manual User guide

Bulletin 280/281 Programmable Parameters 3-17
Misc. Group
OutB DN IdlValue
This parameter determines the
state that Output B assumes
when the network is idle and
Parameter 43 is set to “0”
0 = Open
1 = Close
Parameter Number 44
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Keypad Mode
This parameter selects if the
keypad operation is maintained
or momentary
0= Maintained
1= Momentary
Parameter Number 45
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Keypad Disable
This parameter disables all
keypad function except for the
“OFF” and “RESET” buttons
0=Not Disabled
1=Disabled
Parameter Number 46
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Set to Defaults
This parameter if set to 1 will set
the device to the factory defaults
0=No Operation
1=Set to Defaults
Parameter Number 47
Access Rule GET/SET
Data Type BOOL
Group Misc.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Base Enclosure
Indicates the ArmorStart Base
unit enclosure rating
Bit 0 = IP67
Bit 1 = Nema 4X
Bit 2-15 = Reserved
Parameter Number 56
Access Rule GET
Data Type WORD
Group Misc.
Units
MinimumValue 0
Maximum Value 65535
Default Value 0