Safety Version - User Manual User guide

3-14 Bulletin 280/281 Programmable Parameters
User I/O
Off-to-On Delay
This parameter allows the
installer to program a time
duration before an input is
reported “ON”
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
On-to-Off Delay
This parameter allows the
installer to program a time
duration before an input is
reported “OFF”
Parameter Number 31
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
In Sink/Source
This parameter allows the
installer to program the inputs to
be sink or source.
0=Sink
1=Source
Parameter Number 32
Access Rule GET/SET
Data Type BOOL
Group User I/
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltState
This parameter in conjunction
with Parameter 34 defines how
Output A will respond when a
protection trip occurs. When set
to “1”, Output A continues to
operate as command via the
network. When set to “0”, Output
A will open or close as
determined by setting in
Parameter 34
Parameter Number 33
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units
Minimum Value 0
Maximum Value 1
Default Value 0