Safety Version - User Manual User guide
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers 4-61
EM Brk Off Delay
Sets the time the drive will remain at minimum frequency before ramping to the
commanded frequency and energizing the brake coil relay when Parameter 137 (Stop
Mode) is set to option 8 or 9.
Parameter Number 260
Related Parameters 137
Access Rule GET/SET
Data Type UNIT
Group Advanced Setup
Units 0.01 sec
Minimum Value 0.01 sec
Maximum Value 10 sec
Default Value 0.0 sec
EM Brk On Delay
Sets the time the drive will remain at minimum frequency before stopping and de-
energizing the brake coil relay when Parameter 137 (Stop Mode) is set to option 8 or
9.
Parameter Number 261
Related Parameters 137
Access Rule GET/SET
Data Type UNIT
Group Advanced Setup
Units 0.01 sec
Minimum Value 0.01 sec
Maximum Value 10.00 sec
Default Value 0.0 sec
MOP Reset Sel
Sets the drive to save the current MOP Reference command.
0 = Zero MOP Ref
This option clamps Parameter 169 (Internal Freq) at 0.0 Hz when drive is not running.
1 = Save MOP Ref (Default)
Reference is saved in Parameter 169 (Internal Freq).
Parameter Number 262
Related Parameters 169
Access Rule Get/Set
Data Type UINT
Group Advanced Program Group
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Frequency
Time
Minimum Freq
260 [EM Brk Off Delay]
261 [EM Brk On Delay]
Stop
Commanded
Start
Commanded
EM Brk
De-Energized (On)
Drive StopsEM Brk
Energized (Off)
Ramp Accel
Ramp Decel