Safety Version - User Manual User guide
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers 4-37
Accel Time 2
When active, sets the rate of acceleration for all speed increases except for jog.
Parameter Number 167
Related Parameters
139, 151, 152, 153, 154,
170…173, 174…177,
240…247
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1 sec
Minimum Value 0.0
Maximum Value 600.0
Default Value 20.0
Decel Time 2
When active, sets the rate of deceleration for all speed decreases except for jog.
Parameter Number 168
Related Parameters
140, 151, 152, 153, 154,
170…173, 174…177,
240…247
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1 sec
Minimum Value 0.0
Maximum Value 600.0
Default Value 20.0
Internal Freq
Provide the frequency command to drive when Parameter 138 (Speed Reference) is
set to 1 Internal Freq. When enabled, this parameter will change the frequency
command in real time.
Parameter Number 169
Related Parameters 138, 162
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 400.0
Default Value 60.0
Maximum Freq
Accel Time
-------------------------------------- A ccel Rate=
Parameter 135
(Maximum Freq)
Speed
Param.
139 or
167
(Accel
Time x)
0
0
Time Param.
140 or
168
(Decel
Time x)
Acceleration
Deceleration
Maximum Freq
Decel Time
-------------------------------------- D ecel Rate=
Parameter 135
(Maximum Freq)
Speed
Param.
139 or
167
(Accel
Time x)
0
0
Time Param.
140 or
168
(Decel
Time x)
Acceleration
Deceleration