Bulletin 283 Programmable Parameters 4-5
Not available on the Bulletin 283A.
Trip Status
This parameter provides trip
identification
Parameter Number 4
Access Rule GET
Data Type WORD
Group DeviceLogix
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Short Circuit
X Overload
————————————— X —— Phase Loss
———————————— X ——— Shorted SCR
——————————— X ———— Phase Rotation
—————————— X ————— Control Power
————————— X —————— I/O Fault
———————— X ——————— Overtemperature
X Phase Imbalance
—————— X —————————Dnet Power Loss
————— X —————————— Internal Comm
———— X ———————————Heatsink Over Temp
——— X ———————————— Eeprom
—— X ————————————— HW Fault
X —————————————— Reserved
X ——————————————— Misc Fault