Bulletin 280/281 Programmable Parameters 3-27
Starter Setup
Table 3.2 FLA Setting Ranges and Default Values (with indicated setting
precision)
% Therm Utilized
This parameter displays the
% Thermal Capacity used
Parameter Number 105
Access Rule GET/SET
Data Type USINT
Group Starter Display
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 0
FLA Setting
The motor’s full load current
rating is programmed in this
parameter
Parameter Number 106
Access Rule GET/SET
Data Type INT
Group Starter Setup
Units xx.x Amps
Minimum Value See Table 3.2
Maximum Value See Table 3.2
Default Value See Table 3.2
FLA Current Range (A)
Default Value
Minimum Value Maximum Value
0.24 1.2 0.24
0.5 2.5 0.5
1.1 5.5 1.1
3.2 16.0 3.2
Overload Class
This parameter allows the
installer to select the overload
class
1= Overload Class 10
2= Overload Class 15
3= Overload Class 20
Parameter Number 107
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units xx.x Amps
Minimum Value 1
Maximum Value 3
Default Value 1
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number 108
Access Rule GET/SET
Data Type USINT
Group Starter Setup
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 75