2-24 Installation and Wiring
Wiring Power, Control, Safety Monitor Inputs, and Ground Wiring
Table 2.1 provides the power, control, and ground wire capacity and
the tightening torque requirements. The power, control, ground, and
safety monitor terminals will accept a maximum of two wires per
terminal.
Table 2.1 Power, Control, Safety Monitor Inputs, Ground Wire Size, and
Torque Specifications
Terminals Wire Size Torque Wire Strip Length
Power
and
Ground
Primary/Secondary
Terminal:
1.5…4.0 mm
2
(#16 …#10 AWG)
Primary Terminal:
10.8 lb.-in.
(1.2 N•m)
Secondary Terminal:
4.5 lb.-in
(0.5 N•m)
0.35 in. (9 mm)
Control and Safety
Monitor Inputs
1.0 mm
2
…4.0 mm
2
(#18…#10 AWG)
6.2 lb.-in
(0.7 N•m)
0.35 in. (9 mm)