User Manual

A-14 Specifications
ArmorConnect™ Three-Phase
Power Media
Trunk Cables
Specifications
Dimensions
Dimensions are approximate. Illustrations are not drawn to scale.
Certifications
Standards Compliance UL 2237
Mechanical
Coupling Nut Black Anodized Aluminum or 316 Stainless Steel
Housing Black PVC
Insert Black PVC
Cable Diameter 0.775 in. +/- 0.12 in. (19.68 mm +/- 0.5 mm)
Electrical
Contacts Copper Alloy with Gold over Nickel Plating
Cable Black PVC, dual rated UL TC/Open Wiring and STOOW
Cable Rating 600V AC/DC
Assembly Rating
600V @ 25 A, Symmetrical Amps RMS Fault: 65 kA when
used with Class CC, T, or J type fuses
Environmental
Enclosure Type Rating IP67, NEMA 4; IP69K 1200 psi washdown
Operating Temperature
UL Type TC 600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or
MTW 600V 90 °C or STOOW 105 °C 600V -
CSA STOOW 600V FT2
88.9 (3.50)
38.6
(1.52)
Female straight
(1.95 - 2.25)
(2.94)
(1.52)
74.7
49.5 - 57.1
38.6
Female 90 deg.
88.9 (3.50)
38.6
(1.52)
Male straight
(1.95 - 2.25)
(2.94)
(1.52)
74.7
49.5 - 57.1
38.6
Male 90 deg.