6-36 Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Table 6.5 Analog Output Options
Note: Only output range 0…10V applies with the factory installed
A10 option.
Options 5…14, 16, 17, 19, and 20 are not valid options.
Analog Out Sel
Sets the analog output signal (0…10V). The output is used to provide a signal that is
proportional to several drives
Parameter Number 165
Related Parameters 135, 166
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units
See Table for details
Minimum Value
Maximum Value
Default Value
Options Output Range
Minimum Output
Value
Maximum Output Value A066
(Analog Out High)
DIP Switch Position
Related
Parameter
0 OutFreq 0…10 0…10V 0V = 0 Hz P035 (Maximum Freq) 0…10V 101
1 OutCurr 0…10 0…10V 0V = 0 Amps 200% Drive Rated Output Current 0…10V 103
2 OutVolt 0…10 0…10V 0V = 0 Volts 120% Drive Rated Output Volts 0…10V 104
3 OutPowr 0…10 0…10V 0V = 0 kW 200% Drive Rated Power 0…10V 122
4 TstData 0…10 0…10V 0V = 0000 65535 (Hex FFFF) 0…10V 119
5 OutFreq 0…20 0…20 mA 0 mA = 0 Hz P035 (Maximum Freq) 0…20 mA 101
6 OutCurr 0…20 0…20 mA 0 mA = 0 Amps 200% Drive Rated Output Current 0…20 mA 103
7 OutVolt 0…20 0…20 mA 0 mA = 0 Volts 120% Drive Rated Output Volts 0…20 mA 104
8 OutPowr 0…20 0…20 mA 0 mA = 0 kW 200% Drive Rated Power 0…20 mA 122
9 TstData 0…20 0…20 mA 0 mA = 0000 65535 (Hex FFFF) 0…20 mA 119
10 OutFreq 4…20 4…20 mA 4 mA = 0 Hz P035 (Maximum Freq) 0…20 mA 101
11 OutCurr 4…20 4…20 mA 4 mA = 0 Amps 200% Drive Rated Output Current 0…20 mA 103
12 OutVolt 4…20 4…20 mA 4 mA = 0 Volts 120% Drive Rated Output Volts 0…20 mA 104
13 OutPowr 4…20 4…20 mA 4 mA = 0 kW 200% Drive Rated Power 0…20 mA 122
14 TstData 4…20 4…20 mA 4 mA = 0000 65535 (Hex FFFF) 0…20 mA 119
15 OutTorq 0…10 0…10V 0V = 0 Amps 200% Drive Rated FLA 0…10V 129
16 OutTorq 0…20 0…20 mA 0 mA = 0 Amps 200% Drive Rated FLA 0…20 mA 129
17 OutTorq 4…20 4…20 mA 4 mA = 0 Amps 200% Drive Rated FLA 0…20 mA 129
18 Setpnt 0…10 0…10V 0V = 0% 100.0% Setpoint Setting 0…10V 209
19 Setpnt 0…20 0…20 mA 0 mA = 0% 100.0% Setpoint Setting 0…20 mA 209
20 Setpnt 4…20 4…20 mA 4 mA = 0% 100.0% Setpoint Setting 0…20 mA 209
Analog Out High
Scales the maximum output value for parameter 165 source setting
Parameter Number 166
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units %
Minimum Value 0%
Maximum Value 800%
Default Value 100%