Bulletin 284 Programmable Parameters for Sensorless Vector Controllers 6-15
User I/O Group
➊Not available with the Bulletin 284A.
Off-to-On Delay ➊
This parameter allows the installer to program a time duration before being reported
ON.
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
On-to-Off Delay ➊
This parameter allows the installer to program a time duration before being reported
OFF.
Parameter Number 31
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
In Sink/Source ➊
This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source
Parameter Number 32
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltState
This parameter in conjunction with Parameter 34 defines how Output A will respond
when a trip. When set to 1, Output A continue to operate as command via the
network. When set to 0, Output A will open or close as determined by setting in
Parameter 34.
Parameter Number 33
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltValue
This parameter determines the state the Out A assumes when a trip occurs and
Parameter 33 is set to 0.
0 = Open
1 = Close
Parameter Number 34
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0