User Manual
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-49
Fault Clear
Resets a fault and clears the fault queue. Used primarily to clear a fault over
network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters 107…109 [Fault x Code])
Parameter Number 200
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units —
Minimum Value 0
Maximum Value 2
Default Value 0
Program Lock
Protects parameters against change by unauthorized personnel.
0 = Unlocked
1 = Locked
Parameter Number 201
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Testpoint Sel
Used by Rockwell Automation field service personnel.
Parameter Number 202
Related Parameters 119
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 1 Hex
Minimum Value 0
Maximum Value FFFF
Default Value 400
Comm Data Rate
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number 203
CommNode Addr
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number 204
Comm Loss Action
Selects the drive’s response to a loss of the communication connection or excessive
communication errors.
0 = Fault (Default)
Drive will fault on an F81 Comm Loss and coast to stop
1 = Coast Stop
Stops drive via coast to stop
2 = Stop
Stops via Parameter 137 (Stop Mode) setting
3 = Continu Last
Drive continues operating at communication commanded speed saved in RAM
Parameter Number 205
Related Parameters 115, 137, 206
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units —
Minimum Value 0
Maximum Value 3
Default Value 0
Stop drive before changing this parameter.