User Manual
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-47
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive
1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2. Set Parameter 193 (AutoRstrt Delay) to 0.
ATTENTION
!
Equipment damage and/or personal injury may result if this parameter is used
in an inappropriate application. Do not use this function without considering
applicable local, national, and international codes, standards, regulations, or
industry guidelines.
Auto Rstrt Delay
Sets time between restart attempts when Parameter 192 (Auto Rstrt Tries) is set to a
value other than zero.
Parameter Number 193
Related Parameters 192
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1 sec
Minimum Value 0.0
Maximum Value 300.0 sec
Default Value 1.0 sec
Start at PowerUp
Enables/disables a feature that allows a Start or Run command to automatically
cause the drive to resume running at command speed after the drive input is
restored. Requires a digital input configured Run or Start and a valid start contact.
This parameter will not function if Parameter 136 (Start Source) is set to 4 2-W High
Speed.
0 = Disabled
1 = Enabled
Parameter Number 194
Related Parameters 192
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Stop drive before changing this parameter.
ATTENTION
!
Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use
this function without considering applicable local, national, and
international codes, standards, regulations, or industry
guidelines.