Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-45
Figure 5.3 Overload Trip Curves
Maximum Voltage
Sets the highest voltage the drive will output.
Parameter Number 188
Related Parameters 104
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 1V AC
Minimum Value 20V AC
Maximum Value Drive Rated Volts
Default Value Drive Rated Volts
Current Limit
Maximum output current allowed before current limiting occurs
Parameter Number 189
Related Parameters 133
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1 A
Minimum Value 0.1 A
Maximum Value Drive rated amps X 1.8
Default Value Drive rated amps X 1.5
Motor OL Select
Drive provides Class 10 motor overload protection. Setting 0…2 select the derating
factor for I
2
t overload function.
0 = No Derate
1 = Min. Derate
2 = Max. Derate
Parameter Number 190
Related Parameters 132
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 1
Minimum Value 0
Maximum Value 2
Default Value 0
% of P132 (Motor NP Hertz) % of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)