User Manual
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-37
Accel Time 1
Sets the rate of acceleration for all speed increases.
Parameter Number 139
Related Parameters
138, 140, 151, 152, 167,
170…173
Access Rule GET/SET
Data Type UINT
Group Basic Program Setup
Units 0.1 sec
Minimum Value 0.0 sec
Maximum Value 600.0 sec
Default Value 10.0 sec
Decel Time 1
Sets the rate of deceleration for all speed decreases.
Parameter Number 140
Related Parameters
138, 139, 151, 152, 168,
170…173
Access Rule GET/SET
Data Type UINT
Group Basic Program Setup
Units 0.1 sec
Minimum Value 0.1 sec
Maximum Value 600.0 sec
Default Value 10.0 sec
Reset To Defaults
Resets all parameter values to factory defaults.
0 = Ready/Idle (Default)
1 = Factory Rset
Parameter Number 141
Access Rule GET/SET
Data Type BOOL
Group Basic Program Group
Units —
Minimum Value 1
Maximum Value 1
Default Value 0
Maximum Freq
Accel Time
-------------------------------------- A ccel Rate=
Maximum Freq
Decel Time
-------------------------------------- D ecel Rate=
Stop drive before changing this parameter.
Motor OL Ret
Enables/disables the Motor overload Retention function. When Enabled, the value
held in the motor overload counter is saved at power-down and restored at power-
up. A change to this parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled
Parameter Number 143
Access Rule GET/SET
Data Type BOOL
Group Basic Program Group
Units —
Minimum Value 0
Maximum Value 1
Default Value 0