User Manual
5-36 Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
Maximum Freq
Sets the Highest frequency the drive will output continuously.
Parameter Number 135
Related Parameters
101, 102, 113, 134, 178, 211,
213, 215
Access Rule GET/SET
Data Type UINT
Group Basic Program Setup
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 240
Default Value 60.0
Start Source
Sets the control scheme used to start the Bulletin 284 ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
Parameter Number 136
Related Parameters 112 and 137
Access Rule GET/SET
Data Type UINT
Group Basic Program Setup
Units —
Minimum Value 0
Maximum Value 5
Default Value 5
Stop Mode
Valid Stop Mode for the Bulletin 284 ArmorStart are the following:
0 = Ramp, CF Ramp to Stop. Stop command clears active fault.
1 = Coast, CF Coast to Stop. Stop command clears active fault.
2 = DC Brake,CF DC Injection Braking Stop. Stop command clears active fault.
3 = DCBrkAuto, CF DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if the drive detects that the motor is stopped. Stop command clears
active fault
4 = Ramp Ramp to Stop
5 = Coast Coast to Stop
6 = DC Brake DC Injection Braking Stop
7 = DC BrakeAuto DC Injection Stop with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded
Parameter Number 137
Related Parameters 136, 180, 182, 205
Access Rule GET/SET
Data Type UINT
Group Basic Program Setup
Units —
Minimum Value 0
Maximum Value 7
Default Value 0
Speed Reference
Valid Speed References for the Bulletin 284 ArmorStart are the following:
1 = Internal Freq
4 = Preset Freq
5 = Comm port
Parameter Number 138
Related Parameters
101, 102, 112, 139, 140, 151,
152, 169, 170…173, 210,
211, 213, 232
Access Rule GET/SET
Data Type UINT
Group Basic Program Setup
Units —
Minimum Value 0
Maximum Value 5
Default Value 5
Stop drive before changing this parameter.
Stop drive before changing this parameter.