User Manual
5-28 Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
Zone #2 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If
consumed data is not received in 4 times this value, the zone connection will time
out and “Zone #2 Health” will report 1 = Not Healthy.
Parameter Number 87
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units msec
Minimum Value 0
Maximum Value 65535
Default Value 75
Zone #3 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If
consumed data is not received in 4 times this value, the zone connection will time
out and “Zone #3 Health” will report 1 = Not Healthy.
Parameter Number 88
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units msec
Minimum Value 0
Maximum Value 65535
Default Value 75
Zone #4 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If
consumed data is not received in 4 times this value, the zone connection will time
out and “Zone #4 Health” will report 1 = Not Healthy.
Parameter Number 89
Access Rule GET/SET
Data Type UNIT
Group ZIP Parameters
Units msec
Minimum Value 0
Maximum Value 65535
Default Value 75
Zone #1 Control
Zone 1 Control Word. Default Bits 0 and 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
Parameter Number 90
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 65535
Default Value 75
Zone #2 Control
Zone 2 Control Word. Default Bits 0 and 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages
Parameter Number 91
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 3
Default Value 3