5-26 Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
Zone #4 Health
Read Only consumed connection status for zone 4
0 = Healthy
1 = Unhealthy
Parameter Number 77
Access Rule GET
Data Type BOOL
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 1
Default Value 0
Zone #1 Mask
Bit enumerated consumed data mask for zone 1. Each bit represents a byte in
consumed data up to 8 bytes in length. If a mask bit is set, the corresponding
consumed data byte is placed in the DeviceLogix data table
Parameter Number 78
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 255
Default Value 0
Zone #2 Mask
Bit enumerated consumed data mask for zone 2. Each bit represents a byte in
consumed data up to 8 bytes in length. If a mask bit is set, the corresponding
consumed data byte is placed in the DeviceLogix data table
Parameter Number 79
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 255
Default Value 0
Zone #3 Mask
Bit enumerated consumed data mask for zone 3. Each bit represents a byte in
consumed data up to 8 bytes in length. If a mask bit is set, the corresponding
consumed data byte is placed in the DeviceLogix data table
Parameter Number 80
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 255
Default Value 0
Zone #4 Mask
Bit enumerated consumed data mask for zone 4. Each bit represents a byte in
consumed data up to 8 bytes in length. If a mask bit is set, the corresponding
consumed data byte is placed in the DeviceLogix data table
Parameter Number 81
Access Rule GET/SET
Data Type BYTE
Group ZIP Parameters
Units
—
Minimum Value 0
Maximum Value 255
Default Value 0