User Manual
Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-19
OutB DN FltValue
This parameter determines the state that Output B assumes when a DeviceNet
network fault occurs and Parameter 41 is set to 0.
0 = Open
1 = Close
Parameter Number 42
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutB DN IdlState
This parameter in conjunction with Parameter 44 defines how Output B will respond
when the DeviceNet network is idle. When set to 0, Output B will open or close as
determined by the setting in Parameter 44.
The DN Flt parameters supersede the Dn Idl parameters.
Parameter Number 43
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutB DN IdlValue
This parameter determines the state that Output B assumes when the network is
idle and Parameter 43 is set to 0.
0 = Open
1 = Close
Parameter Number 44
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0