Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-17
➊ Not available on Bulletin 284A units. .
In Sink/Source
This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source
Parameter Number 32 ➊
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltState
This parameter in conjunction with Parameter 34 defines how Output A will respond
when a trip. When set to 1, Output A continue to operate as command via the
network. When set to 0, Output A will open or close as determined by setting in
Parameter 34.
Parameter Number 33
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltValue
This parameter determines the state the Out A assumes when a trip occurs and
Parameter 33 is set to 0.
0 = Open
1 = Close
Parameter Number 34
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA DN FltState
This parameter in conjunction with Parameter 36 defines how Output A will respond
when a DeviceNet network fault occurs. When set to 1, Output A will hold state prior
to trip occurrence. When set to 0, Output A will open or close as determined by
setting in Parameter 36.
Parameter Number 35
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA DN FltValue
This parameter determines the state that Output A assumes when a DeviceNet
network fault occurs and Parameter 35 is set to 0.
0 = Open
1 = Close
Parameter Number 36
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0