5-16 Bulletin 284 Programmable Parameters for Volts per Hertz Controllers
Not available on Bulletin 284A units.
User I/O Group
Bit
Warning
1514131211109876543210
XReserved
XReserved
XReserved
XReserved
XReserved
X Control Power
XIO Warning
XReserved
X Phase Imbalance
X DeviceNet
X Reserved
X Reserved
X Reserved
X Hardware
X Reserved
X Reserved
Off-to-On Delay
This parameter allows the installer to program a time duration before being reported
ON.
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
On-to-Off Delay
This parameter allows the installer to program a time duration before being reported
OFF.
Parameter Number 31
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0