Bulletin 284 Programmable Parameters for Volts per Hertz Controllers 5-9
DeviceNet Group
Autobaud Enable
When this parameter is enabled, the device will attempt to determine the network
baud rate and set its baud rate to the same, provided network traffic exists. At least
one node with an established baud rate must exist on the network for autobaud to
occur.
0 = Disable
1 = Enable
Parameter Number 10
Access Rule GET/SET
Data Type BOOL
Group DeviceNet
Units —
Minimum Value 0
Maximum Value 1
Default Value 1
Consumed I/O Assy
This parameter selects the format of the I/O data consumed
Parameter Number 11
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units —
Minimum Value 0
Maximum Value 188
Default Value 164
Produced I/O Assy
This parameter selects the format of the I/O data produced.
Parameter Number 12
Access Rule GET/SET
Data Type USINT
Group DeviceNet
Units —
Minimum Value 0
Maximum Value 190
Default Value 165
Prod Assy Word 0
This parameter is used to build bytes 0-1 for produced assembly 120.
Parameter Number 13
Access Rule GET/SET
Data Type INT
Group DeviceNet
Units —
Minimum Value 0
Maximum Value 216
Default Value 1
Produced Assy Word 1
This parameter is used to build bytes 2-3 for produced assembly 120
Parameter Number 14
Access Rule GET/SET
Data Type INT
Group DeviceNet
Units —
Minimum Value 0
Maximum Value 216
Default Value 4