4-30 Bulletin 283 Programmable Parameters
Table 4.2 FLA Setting Ranges and Default Values (with indicated setting
precision)
➊ Recommended maximum start time is 15 seconds.
➋ Recommended maximum current limit setting is 350%.
FLA Current Range (A)
Default Value
Minimum Value Maximum Value
1.1 3.0 1.1
3.0 5.5 3.0
5.3 7.6 5.3
6.3 16.0 6.3
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number 108
Access Rule GET/SET
Data Type USINT
Group Soft Start Setup
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 75
Start Time ➊
This parameter allows the
installer to select the start time of
1…45 seconds
Parameter Number 109
Access Rule GET/SET
Data Type USINT
Group Soft Start Setup
Units Sec
Minimum Value 1
Maximum Value 45
Default Value 10
Start Mode
This parameter allows the
installer to select either soft stop
or current limit
1= Current Limit
0= Soft Start
Parameter Number 110
Access Rule GET/SET
Data Type BOOL
Group Soft Start Setup
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Current Limit ➋
This parameter allows the
installer to select the value of the
current limit setting of
150…600% of the full load amps
Parameter Number 111
Access Rule GET/SET
Data Type UINT
Group Soft Start Setup
Units % of Motor FLA
Minimum Value 150
Maximum Value 600
Default Value 350