Bulletin 283 Programmable Parameters 4-29
Soft Start Setup
Phase C Current
This parameter provides the
current of Phase C measured in
increments of 1/10
th
of an
ampere
Parameter Number 103
Access Rule GET/SET
Data Type INT
Group Soft Start Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
Average Current
This parameter provides the
average current measured in
increments of 1/10
th
of an
ampere
Parameter Number 104
Access Rule GET/SET
Data Type INT
Group Soft Start Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
% Therm Utilized
This parameter displays the
% Thermal Capacity used
Parameter Number 105
Access Rule GET/SET
Data Type USINT
Group Soft Start Display
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 0
Overload Class
This parameter allows the
installer to select the overload
class
1= Overload Class 10
Parameter Number 107
Access Rule GET/SET
Data Type INT
Group Soft Start Display Setup
Units Amps
Minimum Value 1
Maximum Value 1
Default Value 1
FLA Setting
The motor’s full load current
rating is programmed in this
parameter
Parameter Number 106
Access Rule GET/SET
Data Type INT
Group Soft Start Setup
Units A
Minimum Value See Table 3.2
Maximum Value See Table 3.2
Default Value See Table 3.2