User Manual
Bulletin 283 Programmable Parameters 4-17
➊ Not available on the Bulletin 283A.
On-to-Off Delay
This parameter allows the
installer to program a time
duration before an input is
reported “OFF”
Parameter Number 31
➊
Access Rule GET/SET
Data Type UINT
Group User I/O
Units ms
Minimum Value 0
Maximum Value 65.000
Default Value 0
In Sink/Source
This parameter allows the
installer to program the inputs to
be sink or source.
0=Sink
1=Source
Parameter Number 32 ➊
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltState
This parameter in conjunction
with Parameter 34 defines how
Output A will respond when a
protection trip occurs. When set
to “1”, Output A continues to
operate as command via the
network. When set to “0”, Output
A will open or close as
determined by setting in
Parameter 34
Parameter Number 33
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltValue
This parameter determines the
state the Out A assumes when a
trip occurs and Parameter 33 is
set to “0”
0 = Open
1 = Close
Parameter Number 34
Access Rule GET/SET
Data Type BOOL
Group User I/O
Units —
Minimum Value 0
Maximum Value 1
Default Value 0