User Manual

Bulletin 283 Programmable Parameters 4-13
Not available on the Bulletin 283A.
PrFlt Reset Mode
This parameter configures the
Protection Fault reset mode.
0= Manual
1= Automatic
Parameter Number 23
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Pr Fault Enable
This parameter enables the
Protection Fault by setting the bit
to 1
Parameter Number 24
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 16383
Default Value 8195
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Short Circuit
X Overload
————————————— X —— Phase Loss
———————————— X ——— Shorted SCR
——————————— X ———— Phase Rotation
—————————— X ————— Control Power
————————— X —————— I/O Fault
———————— X ——————— Overtemperature
X Phase Imbalance
—————— X —————————Dnet Power Loss
————— X —————————— Internal Com
———— X ———————————SCR Heatsink Temp
——— X ———————————— Eeprom
—— X ————————————— HW Fault
X —————————————— Reserved
X ——————————————— Misc Fault